Module Properties dialog box - Calibration page parameters (5094-IRT8S, 5094-IRT8SXT, 5094-IF4IHS, 5094-IF4IHSXT, 5094-OF4IHS, 5094-OF4IHSXT)

The Calibration page includes these parameters:
Parameter
Description
Channel
Shows the channel number.
Calibration Range
Shows the range currently configured for the channel. Ranges display according to the
Input Range
or
Output Range
selected.
Calibration Gain
Shows the calibration gain value as reported by the module.
Offset
Shows the offset in units (ohm, mV, V, or mA) as reported by the module.
Last Calibration Date
Shows the last calibration date for the channel. The time and date listed here is based on the time on the computer running the
Logix Designer
application.
Calibration Status
Shows the status of the calibration per input range or output range and channel as the calibration occurs. Valid values include:
  • OK
  • Error
Revert to Factory Calibration
Select to begin the process of reverting to the corresponding factory gain and offset values of the range for which the selected channels are configured. The status of the reverting is appears in
Calibration Status
column.
Revert to Factory Calibration
is enabled when the module is online with the controller, inhibited, and safety reset is performed.
Start Calibration
Select to begin the calibration process.
Start Calibration
is enabled when the module is online with the controller, inhibited, and safety reset is performed.