Channel0x Diagnostics parameters
Channel0x Diagnostics
includes these parameters:Parameter | Description | Value |
---|---|---|
Fault Exists | Shows whether a fault is present on the device. | 0 = None 1 = Present |
Data Uncertain | Shows the device is operating outside the designed operating range, or data is under manual or override control. | 0 = No 1 = Yes |
Field Power | Shows whether field power is present on the channel. | 0 = Not present 1 = Present |
Field Power On/Off Timestamp | Shows the timestamp of the last time field power turned on or off in YYYY-MM-DD-HH:mm:SS.mmm format.
| A valid time or blank if no event time was recorded. |
SSV Over Current Fault | Shows whether a sensor source voltage over-current is present on the channel. | 0 = None 1 = Present |
Short Circuit Fault | Shows whether a short circuit or over-current fault (greater current at an output than the maximum current level the channel can handle) is present on the channel. | 0 = None 1 = Present |
No Load Fault | Shows whether a no load fault (a signal wire is disconnected from the output or the RTB) is present on the channel. | 0 = None 1 = Present |
Open Wire Fault | Shows whether an open wire fault (an output wire is disconnected) is present on the channel. | 0 = None 1 = Present |
Module Over Temperature Fault | Shows whether the device is operating at a higher temperature than its operating limits. | 0 = Normal 1 = Above normal range |
Overrange Fault | Shows whether a signal overrange fault is present on the channel. | 0 = None 1 = Present |
Underrange Fault | Shows whether a signal underrange fault is present on the channel. | 0 = None 1 = Present |
Fault Timestamp (Short Circuit, No Load, Open Wire, Module Over Temperature, Overrange, Underrange) | Shows the timestamp of the last fault in YYYY-MM-DD-HH:mm:SS.mmm format.
| A valid time or blank if no event time was recorded. |
SSV OverCurrent Timestamp | Shows the timestamp of the last SSV OverCurrent condition in YYYY-MM-DD-HH:mm:SS.mmm format.
| A valid time or blank if no event time was recorded. |
Calibration Timestamp | Shows the timestamp of the last calibration in YYYY-MM-DD-HH:mm:SS.mmm format.
| A valid time or blank if no event time was recorded. |
Range | Shows the range for the most recently calibrated channel. | 0 = -10 V to 10 V 1 = 0 V to 5 V 2 = 0 V to 10 V 3 = 1 V to 5 V 4 = 0 mA to 20 mA 5 = 4 mA to 20 mA 6 = -100 mV to 100 mV 7 = 1 ohm to 500 ohms 8 = 2 ohms to 1000 ohms 9 = 4 ohms to 2000 ohms 10 = 8 ohms to 4000 ohms |
Gain | Shows the channel calibration gain from the last valid calibration. | 32-bit floating point value |
Offset | Shows the channel calibration offset from the last valid calibration. | 32-bit floating point value |