ControlLogix 5590 Environmental Specifications

Environmental Specifications - ControlLogix 5590 Standard Controllers
Attribute
1756-L902TS, 1756-L905TS, 1756-L908TS, 1756-L915TS, 1756-L925TS, 1756-L950TS, 1756-L980TS
Temperature, operating (SIL 2/PLd)
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0 °C ≤ Ta ≤ +60 °C (+32 °F ≤ Ta ≤ +140 °F) for Series C Chassis 0 °C ≤ Ta ≤ +50 °C (+32 °F ≤ Ta ≤ +122 °F) for Series B Chassis
Temperature, operating (SIL 3/PLe)
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0 °C ≤ Ta ≤ +60 °C (+32 °F ≤ Ta ≤ +140 °F) for Series C Chassis 0 °C ≤ Ta ≤ +50 °C (+32 °F ≤ Ta ≤ +122 °F) for Series B Chassis
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F) Chassis Series C and B
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Conformal coated
No
Vibration
IEC 60068-2-6 (Test Fc, Operating)
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Emissions
IEC 61000-6-4
ControlLogix 5590 controllers require a NEMA 1 or equivalent, windowless, metal enclosure.
ESD immunity
IEC 61000-4-2
Radiated RF immunity
IEC 61000-4-3
EFT/B Immunity
IEC 61000-4-4
Shielded cable is recommended for a coarse Update Rate (CUR)/ Requested Packet Interval (RPI) of 6ms or less. To use unshielded cable, the CUR/RPI must be at least 8ms.
Surge Transient Immunity
IEC 61000-4-5
Conducted RF Immunity
IEC 61000-4-6