Replace a CIP Security-enabled 1756-EN4TR Module

WARNING:
Module replacement requires redeployment of the security policy.
To replace a
CIP Security
-enabled 1756-EN4TR module, follow these steps.
  1. If the security policy includes
    FactoryTalk® Linx
    , then remove
    FactoryTalk® Linx
    from the security policy and redeploy the security policy without
    FactoryTalk® Linx
    .
  2. Replace the 1756-EN4TR module in the disqualified chassis as described in Perform a Direct Module Replacement in the Secondary Chassis.
  3. Redeploy the security policy to the 1756-EN4TR module by using the Validate and Deploy option.
  4. If you removed
    FactoryTalk® Linx
    from the security policy in step 1, then add
    FactoryTalk® Linx
    back to the security policy and redeploy the security policy with
    FactoryTalk® Linx
    .
    The new 1756-EN4TR module becomes accessible in
    FactoryTalk® Linx
    .
  5. If the auto-synchronization setting in the Redundancy Module Configuration Tool (RMCT) is not set to Always, then on the Synchronization tab, select Synchronize Secondary.
    Synchronize Secondary button
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.