Remove and Install the IP21/IP54 Roof Vent Fan for Frames 8...15
Replace an IP21/IP54 roof vent fan on a control or input bay with kit catalog number SK-RM-IBFAN1-F8. Follow these steps to remove and install the IP21/IP54 roof vent fan.
- Review the product advisories in Before You Begin.
- Remove power from the system.
- Open the control bay or input bay enclosure door.
- Disconnect the fan P2 connector (A) from connector P12 (B) on the inside of the enclosure.
- Remove the M8 hex nut and washer that secure the ground wire (C) to the inside of the enclosure roof and remove the wire.
- Remove the nine M4 x 10 mm slotted-Torx screws that secure the vent cover (D) to the top of the vent assembly and remove the cover.
- Remove the four M4 hex nuts that secure the fan assembly to the vent (E).
- Lift the side of the fan (F) opposite from the connector and, while holding the fan at an angle to the housing, remove the fan.
- Install the IP21/IP54 roof vent fan in the reverse order of removal.
Provide Feedback