1834-SUP-PWR Supplemental Power Tap Auto-generated Tags

After you configure the device, tags are automatically generated. The data from the input (produced) and output (consumed) assemblies is used as descriptive tag names to simplify programming.
1834-SUP-PWR Supplemental Power Tap Auto-generated Controller Input Tags
Tag
Data Type
Function
DeviceName:I.RunMode
BIT
PLC Status.
0 = Not Run Mode
1 = Run Mode
Run Mode = 0 when DataStatus.Fault bit is set to a 1 or the Run/Idle header in the Exclusive Owner connection is set to Idle.
Run Mode = 0 when DataStatus.Fault bit is set to a 1 or the Run/Idle header in the Exclusive Owner connection is set to Idle.
DeviceName.I. ConnectionFaulted
BIT
PLC Status. Connection to the device is:
0 = Up and working
1 = Not connected.
DeviceName.I.DiagnosticActive
BIT
PLC Status.
0 = No diagnostics active
1 = One or more diagnostic or prognostics thresholds reached, DataStatus.Fault bit is set to a 1 or TripWarnStatus.TripPresent bit is set to a 1
DeviceName.I.DiagSequenceCount
SINT
Controller status. Increases each time that a distinct diagnostic condition is detected. The device increases this value on the rising and falling edges of any of the following conditions:
Each condition that sets the DataStatus.Fault Bit to a 1.
Each condition that sets the TripWarnStatus.TripPresent Bit to a 1.
NOTE:
If the DataStatus.Fault is set because both the TripWarnStatus.NPVoltageTrip bit is set to 1 and the TripWarnStatus.SPOverCurrentTrip bit is set to 1, the DiagSequenceCount is incremented by 2, and when theTripWarnStatus.NPVoltageTrip bit clears, it is incremented by 1 and when the TripWarnStatus.SPOverCurrentTrip bit clears, it is incremented by 1 again.
This value is set to zero on power-up / reset and rolls over after a count of 255 to the value of 1 not a value of 0.
DeviceName.I.Fault
BIT
Device-level data.
0 = Normal good data
1 = Data is bad.
This is a roll-up of all diagnostic conditions that the module can detect that indicates that the signal is not good data.
The device sets this bit to a 1 when TripWarnStatus = InternalFault bit is set to 1
If there is a detailed data type member that indicates a given detected condition, then this Fault member does not itself affect the DiagnosticActive or DiagnosticSequenceCount members. However, if there is not a detailed data type for a given detected condition, then this Fault member triggers both the DiagnosticActive member and increments/decrements the Diagnostic Sequence Count.
DeviceName.I.Uncertain
BIT
0 = No question about data validity
1 = Data validity is questionable
Module is operating outside its designed operating range, or data is under manual or override control.
DeviceName.I.SwitchedPowerActive
BIT
Switched power provides application power for the 100-E contactor coils. Indicates whether the Switched power is Active.
0 = Switched power is not provided to End Nodes
1 = Switched power is switched on
DeviceName.I.TripPresent
BIT
Indicates that the operational trip conditions have been detected by the device.
0 = No trips
1 = Trip condition(s) exists
The device sets this bit to a 1 when the device has detected an operational trip condition.
DeviceName.I.WarningPresent
BIT
Indicates that the operational warning conditions have been detected by the device.
0 = No warnings
1 = Warning condition(s) exists
The device sets this bit to a 1 when the device has detected a warning condition.
DeviceName.I.SwitchedPowerVoltageTrip
BIT
Switched Power has exceeded its design working limit. The Switched Power Voltage Trip is latched and must be unlatched when the trip conditions are removed.
0 = Switched power is not tripped
1 = Trip condition for the Switched power voltage has occurred
DeviceName.I.SwitchedPowerOverCurrentTrip
BIT
Switched Power has exceeded its design working limit. The Switched Power Over Current Trip is latched and must be unlatched when the trip conditions are removed.
0 = Switched power is not tripped
1 = Trip condition for the Switched power current has occurred
DeviceName.I.SwitchedPowerVoltageWarning
BIT
When set indicates that the voltage for the Switched Power has exceeded its design warning limit and may cause the Switched Power Voltage Trip.
0 = Voltage for the Switched power below the warning limit
1 = Voltage for the Switched power above the warning limit
DeviceName.I.SwitchedPowerOverCurrentWarning
BIT
When set indicates that the current for the Switched Power has exceeded its design warning limit and may cause the Network Power Over Current Trip.
0 = Current for the switched power below the warning limit
1 = Current for the switched power above the warning limit
DeviceName.I.SwitchedPowerFault
BIT
When set indicates that the Switched Power Supply cannot detect external 24V input or there is an internal fault on the communications line to the power supply IC
0 = External 24V DC power is detected and communication and initialization of power supply IC is successful.
1 = External 24V DC power is not detected or communication and initialization of power supply IC is faulted.
DeviceName.I.InternalFault
BIT
Indicates internal fault state. For example: the NVS fault power on self tests finished with fault.
DeviceName.I.OperatingHoursAlarm
BIT
If predictive maintenance data is available for the device component, this parameter indicates that the component's remaining life is below the warning threshold.
DeviceName.I.NetworkPowerVoltage
REAL
Actual voltage measurement for the Network Power. Measurement is scaled to user units [VDC].
DeviceName.I.SwitchedPowerVoltage
REAL
Actual voltage measurement for the Switched Power. Measurement is scaled to user units [VDC].
DeviceName.I.SwitchedPowerCurrent
REAL
Actual current measurement for the Switched Power. Measurement is scaled to user units [Amps].
1834-SUP-PWR Supplemental Power Tap Auto-generated Controller Output tags
Tag
Data Type
Function
DeviceName:O.DisableSwitchedPower
BIT
Disables/Enables the Switched power. When disabled, downstream end nodes application power for the 100-E contactor coils is removed.
0 = End Nodes are supplied
1 = End Nodes power is switched off
DeviceName:O.ResetSwitchedPowerTrip
BIT
If the Switched Power trip occurs, a logical "1"" on this member resets the trip.
0 = Trip is not reset
1 = Trip is reset
1834-SUP-PWR Supplemental Power Tap Auto-generated Controller Configuration tags
Tag
Data Type
Function
DeviceName:C.NetworkPowerVoltageWarningEn
BIT
Enable or disable the network power voltage warning. If disabled, the warning does not activate when the voltage exceeds the design warning limit.
0 = Disable
1 = Enable
DeviceName.SwitchedPowerOverCurrentWarningEn
BIT
Enables/Disables the Switched Power Over Current Warning. If disabled the warning is not set when current exceeds the design warning limit.
0 = Disable
1 = Enable
DeviceName.OperatingHoursAlarmEn
BIT
Enables/Disables the Operating Hours Alarm. If disabled the Operating Hours Alarm is not set when the component remaining life crosses the warning threshold.
0 = Disabled
1 = Enabled
DeviceName.RemainingOperatingHoursAlarmLimit
DINT
Defines the remaining hours at which the Operating Hours Alarm is set. If the remaining life counter crosses that threshold user is notified that device component approaches to end of its life.
0 - 100 000. Default is 10,000 hours