Logging view parameters

Parameter
Description
Time-of-use log start day
Displays the current value of time of use (TOU) auto-store day in the power monitor. The current record for the month is automatically stored on this day replacing an older record if the log is full. You may select a different TOU auto-store day using the spinner control. Select
Apply
to set in the power monitor.
Valid values range from 1 through 31 (default).
If offline, the change will take effect when next online.
Energy log
Use these controls to view and modify the parameters related to operation of the energy logging function.
Enable energy log
Determines whether the energy log is enabled. Select the checkbox to change. Select
Apply
to set in the power monitor.
If offline, the change will take effect when next online.
Synchronize energy log with end of demand interval
Indicates the energy log interval is synchronized with the demand end-of-interval event when the radio button is selected. Select the other radio button to use a fixed time interval instead. Select
Apply
to set in the power monitor.
If offline, the change will take effect when next online.
Energy log interval
Indicates the energy log interval in minutes is displayed in the spinner control when the radio button is selected. The energy log interval spinner control is hidden if the energy log interval is synchronized with the demand interval.
When online, use the spinner control to change the energy log interval. Select the other radio button to synchronize the energy log with the demand interval. Select
Apply
to set in the power monitor.
Valid values range from 1 through 60. The default is 15.
If offline, the change will take effect when next online.
Energy log mode
Displays the current energy log mode.
The available values are:
  • 0 = Fill and Stop
  • 1 = Overwrite (default)
Select the desired mode to make a change. Select
Apply
to set in the power monitor.
If offline, the change will take effect when next online.
Clear energy log button
Clears the energy log from the power monitor memory and begins a new energy log when online.
This parameter is disabled when offline.
Clear energy counters button
Clears the energy counters to zero in the power monitor (with firmware revision 3.0 and later) and begins accumulating energy anew.
This parameter is disabled when offline.