Counter0x view parameters

The
Counter0x
view includes these parameters:
Parameter
Description
Member Name
Value
Rollover
Shows the rollover value.
When the counter counts up to this value, it is set to the Rollunder value when the next pulse is received.
O.Counter0x.RolloverValue
-2147483648 to 2147483647 AND greater than the Rollunder value
Rollunder
Shows the rollunder value.
When the counter counts down to this value, it is set to the Rollover value when the next pulse is received.
O.Counter0x.RollunderValue
-2147483648 to 2147483647
Load Count Value
Shows the load count value.
O.Counter0x.LoadCountValue
O.Counter0x.Rollunder ≤ O.Counter0x.LoadCountValue < O.Counter0x.Rollover
Load Revolution Value
Shows the load revolution value.
O.Counter0x.LoadRevolutionValue
-32768 to 32767
Pulses to Average Over
Specifies the number of pulses to average when calculating average frequency, pulse width, and rate.
C.Counter0x.AvgOverPulses
1 to 32767
Engineering Units
Specifies the unit of measure for the counter.
Not applicable
Any string
Scalar
Specifies the scaling value for the counter.
  • Scale count, frequency, and acceleration values to Engineering Units in REAL by multiplying their integer values in pulses by the Scaling value.
  • For example: For motion applications, scale count, frequency, and acceleration to position, velocity, and acceleration/deceleration.
C.Counter0x.Scaling
32-bit floating point value
Reset time-derived values
Determines that a Reset sets the frequency and average frequency, pulse width, and acceleration to zero.
C.Counter0x.ResetTimeDerivedValues
0 = Reset does not reset time-derived values.
1 = Reset resets time-derived values.
Count while owning controller is in Program mode
Determines whether a counter continues counting when the owner-controller is in Program mode.
C.Counter0x.LocalControlEn
0 = Counter does not continue counting.
1 = Counter continues counting.
Invert Counter Direction
Determines whether the counter direction inverts.
C.Counter0x.InvertDirectionInput
0 = Do not invert the counter direction.
1 = Invert the counter direction.
Diagnostics
Opens the diagnostics dialog box to view diagnostic information.