Counter0x - Fault/Program Actions view parameters

The
Fault/Program Actions
view includes these parameters:
Fault actions
Parameter
Description
Member Name
Value
Counter State in Communication Fault Mode
Specifies the counter state in Communication Fault mode.
C.Counter0x.FaultMode
0 = Continue Counting
1 = Hold
2 = User Defined Value
Counts
Specifies the value of the counter in Communication Fault mode. It is available when C.Counter0x.FaultMode is 2.
C.Counter0x.FaultValue
-2147483648 to 2147483647
Reset Stored Values in Communication Fault Mode
Resets the value of the accumulated count in Communication Fault mode.
C.Counter0x.FaultModeStoredValuesReset
0 = Do not reset StoredCount and other Stored0x members for the counter
1 = Reset StoredCount and other Stored0x members for the counter
Program actions
Parameter
Description
Member Name
Value
Counter State in Program Mode
Specifies the counter state in Program mode.
C.Counter0x.ProgMode
0 = Continue Counting
1 = Hold
2 = User Defined Value
Counts
Specifies the value of the counter in Program mode. It is available when C.Counter0x.ProgMode is 2.
C.Counter0x.ProgValue
-2147483648 to 2147483647
Reset Stored Values in Program Mode
Resets the value of the accumulated count in Program mode.
C.Counter0x.ProgModeStoredValuesReset
0 = Do not reset StoredCount and other Stored0x members for the counter
1 = Reset StoredCount and other Stored0x members for the counter
When Communication Fails in Program Mode
Determines the counter state if a communication faults while the device is in Program mode.
C.Counter0x.ProgramToFaultEn
0 = Remain in Program mode
1 = Transition to Communication Fault mode
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.