Pt0x - Digital Timestamp Input parameters (5015-U8IHFTXT)
Pt0x - Digital Timestamp Input
includes these parameters:Parameter | Description |
Disable Point | Disables point configuration. Cleared by default. Select to disable point configuration. |
Sensor Type |
|
Three wire sensor | Enabled only for universal modules. Sets the user wiring to Three Wire Sensor. Cleared by default. Select to set the user wiring to Three Wire Sensor. Clear to set the user wiring to Two Wire Sensor. |
Sourcing power from channel | Enabled only on universal modules. Selected by default. Select to source power from channel. Clear to source power externally and remove diagnostics on Screw A. |
Field power diagnostics |
|
Off -> On filter time | Defines how long an Off to On input transition must remain in the On state before the device considers the transition valid. Available values:
|
On -> Off filter time | Defines how long an On to Off input transition must remain in the Off state before the device considers the transition valid. Available values:
|
Thresholds | Opens Edit Custom Thresholds . Select to edit custom thresholds. |
Enable timestamp latching | Appears when you set Device Definition > Input Data to Timestamp Data.Enables timestamp latching, which does not overwrite device timestamps until acknowledged. Cleared by default. Select to enable timestamp latching. Clear to allow overwriting device timestamps. |
Capture timestamp for: Off → On input transition | Appears when you set Device Definition > Input Data to Timestamp Data.Captures a timestamp for the Off → On input transition. Selected by default. Clear to disable timestamp capture for the Off → On input transition. |
Capture timestamp for: On → Off input transition | Appears when you set Device Definition > Input Data to Timestamp Data.Captures a timestamp for the On → Off input transition. Selected by default. Clear to disable timestamp capture for the On → Off input transition. |
Enable chatter detection | Appears when you set Device Definition > Input Data to Timestamp Data.Enables chatter detection, which ignores chatter from a device that is connected to one of its inputs (for example, rapid transitions from a failed contact) according to the Chatter count and Chatter time setting. Cleared by default.Select to enable chatter detection. |
Chatter count | Appears when you set Device Definition > Input Data to Timestamp Data.Specifies the number of acceptable input transitions that can occur in a given time period before considering the input to be chatter. Valid values range from 2 to 127. |
Chatter time | Appears when you set Device Definition > Input Data to Timestamp Data.Specifies the amount of time, from 1 to 10000 milliseconds, within which the number of input transitions are counted. |
Copy Point Configuration | Opens Copy Point Configuration . Select to copy point configuration to other points. |
Provide Feedback