Inputs view parameters
TIP:
In the
Equivalent
safety input mode, channels in pair have the same configuration value (Channel 1 follows Channel 0 and Channel 3 follows Channel 2).Parameter | Description |
|---|---|
Channel | Indicates the channel to which the configuration applies to. |
Point Mode | Specifies the point input mode for each channel. Valid values include:
Point Mode appears shaded under these conditions:
|
Range | Specifies the input range for each input channel. Valid values include:
Range appears shaded under these conditions:
|
Filter | Specifies the filter options for each input channel. Valid values include:
Filter appears shaded under these conditions:
|
High Engineering | Specifies the high engineering value for each channel. Valid values are from -30000 to 30000 (engineering units). The default value is:
High Engineering appears shaded under these conditions:
Tip: Alarm values must be scaled to the engineering units defined in the Inputs view. |
Low Engineering | Specifies the low engineering value for each channel. Valid values are from -30000 to 30000 (engineering units). The default value defaults to 0 when you change the Range value.Low Engineering appears shaded under these conditions:
Tip: Alarm values must be scaled to the engineering units defined in the Inputs view. |
Sensor Power Supply | Specifies how each sensor is powered. Valid values include:
Tip: Select Module to supply power to the sensors connected to the Point Guard Analog Input device. This allows the device to detect a loss of sensor power.IMPORTANT: When a channel is configured for the Module sensor power, a sensor power diagnostic is executed on the channel at power-up to make sure the sensor is operational and that it draws current within the half second interval of the test. The test also verifies that the channel is not over or under current. |