Ch0x view parameters (HART Input)

The
Ch0x
view (HART Input) includes these parameters:
Parameter
Description
Input Type
Displays the input type for the channel, which is Current (mA).
Input Range
Sets the input range for the Current (mA) input type.
Available options are:
  • 0 mA to 20 mA
  • 4 mA to 20 mA
Enable HART
Enables HART functionality on the channel.
Engineering Units
Sets the unit of measurement for
High Engineering
and
Low Engineering
and for the channel’s input value.
High Signal
Sets one of the four constants in the scaling equation.
High Signal
is in terms of the input signal units and corresponds to
High Engineering
when scaled.
High Signal
must be greater than
Low Signal
.
High Engineering
Sets one of the four constants in the scaling equation.
High Engineering
corresponds to
High Signal
and helps determine the engineering units that the signal values scale into.
Low Signal
Sets one of the four constants in the scaling equation.
Low Signal
is in terms of the input signal units and corresponds to
Low Engineering
when scaled.
Low Engineering
Sets one of the four constants in the scaling equation.
Low Engineering
corresponds to
Low Signal
and helps determine the engineering units that the signal values scale into.
Digital Filter
Sets the time constant for a first order lag filter used to smooth noise transients on the input with a range from 0 through 32767. When set to 0, no filtering takes place.
Enable Diagnostics
Enables short circuit and open wire detection on the channel when selected.