DeviceNet Scan List
TIP:
Functions on this page are only available when the
project is online.
Scanner Mode
Displays the scanner mode of the module.
Valid values are IDLE and RUN.
Enable AutoScan
Enables or disables the AutoScan feature.
When set to enable (and the previous value was disable), the existing scan list shall
be cleared.
Any set access to the Scan List from a tool such as RSNetworx shall disable AutoScan.
This value can be set only when the scanner is in IDLE mode and is saved to
non-volatile memory immediately.
Bytes per Node
Choose the size of the input and output memory maps that the scanner will allocate
for each device it detects on the network during AutoScan.
Valid values range from 1 to 32 bytes per node.
Devices in Scan List
Indicates which device addresses the scanner has in its internal scan list.