Power Jumper Configuration—Frame 7

PowerFlex 755T products contain protective MOVs, common mode capacitors, and discharge resistors. To guard against drive damage and/or operational problems, these devices must be properly configured according to the tables in this section.

Common Mode Capacitor, MOV, AC EMI Capacitor, and Discharge Resistor Circuits

The following frame 7 power jumpers are discussed in this section.
  • PE-A – MOV on the AC precharge control circuit board
  • PE-A1 – MOV on the TVSS module
  • PE-A1 – MOV on the TVSS module PE-A2 – Common mode capacitors on the AC common mode filter circuit board
  • DR – DC bus conditioner capacitor discharge resistor
Common Mode Capacitor, MOV, AC EMI Capacitor, and Discharge Resistor Circuits—Frame 7
Image that shows the recommended power jumper settings for drive frame 7.
DC Bus Conditioner Discharge Resistor—Frame 7
Image that shows the recommended discharge resistor jumper settings for drive frame 7.
IMPORTANT: The default power jumper settings are:
  • All power jumpers are installed in the connected (IN) position.
  • All power jumpers are installed in the disconnected (OUT) position when the bus conditioner for marine applications (-P51) is selected.
ATTENTION:
Risk of equipment damage exists.
The drive power source type must be accurately determined. The power jumpers must be configured for the power source type according to the recommendations in the PowerFlex 755T Input Product RF Emission Compliance and Installation Requirements.
ATTENTION:
Risk of equipment damage exists.
Hazard of equipment damage exists if jumpers are not properly disconnected or are set differently between power and LCL filter modules. Secure a disconnected jumper in the socket or on the insulated spacer that is provided and verify that all modules are configured identically.
PowerFlex 755TL/TR Power Jumpers—Frame 7
Grounding Scheme
EMC Option
PE-A
PE-A1
PE-A2
DR
MOV on the AC Precharge Control Circuit Board
MOV in the TVSS Module
Common Mode Caps on the AC Common Mode Filter Circuit Board
Discharge Resistor on the DC Bus Conditioner
Factory Default
C3
Connected (In)
Connected (In)
Connected (In)
Connected (In)
Grounded
C2
Connected (In)
Connected (In)
Connected (In)
Connected (In)
Grounded
C3
Connected (In)
Connected (In)
Connected (In)
Connected (In)
Ungrounded/High-resistance Ground
AC fed ungrounded
Impedance grounded
B phase ground
Disconnected (Out)
Disconnected (Out)
Disconnected (Out)
Connected (In)
Marine Ungrounded / High Resistance Ground
Disconnected (Out)
Disconnected (Out)
Disconnected (Out)
Disconnected (Out)
The EMC C2 option listed meets EN61800-3 Category C2 for conducted emissions.
Ungrounded and high-resistance ground systems do not meet the EMC Directive due to the disconnected jumper positions.