Module Data Quality Reporting
The module indicates the quality of channel data that is returned to the
owner-controller. Levels of data quality are reported via module input tags.
IMPORTANT:
Once the condition that causes the
Fault
or Uncertain
tag to change
to 1 is removed, the tag automatically resets to 0. You cannot change the status
of the tags. The Studio 5000 Logix Designer application controls the tags. Keep
in mind that in some system configurations, the tag is not reset immediately
after the condition is removed. The tag typically resets after a small
delay.The following inputs tags indicate the level of data quality.
- Fault – When theFaulttag is set, it indicates that the reported channel data is inaccurate and cannot be trusted for use in your application. Do not use the reported channel data for control. If the tag is set to 1, you must troubleshoot the module to correct the cause of the inaccuracy.
- Uncertain – When theUncertaintag is set, it indicates that the reported channel data can be inaccurate but the degree of inaccuracy is unknown. Do not use the reported channel data for control.
Channel Communication Mode | Tag Name | Causes |
|---|---|---|
Generic ASCII | Ix.ASCII.Fault | The causes of inaccurate data include the following:
|
Ix.ASCII.Uncertain | None | |
Modbus Master | Ixx.Fault | SA power loss |
Ixx.Uncertain | Any Modbus command uncertain | |
Modbus Slave | Ix.Slave.Fault | SA power loss |