Convert to Integer (BCD_TO)
    This table lists the controllers and applications that support this instruction.
          
  
    
Architecture  | Standard applications  | Safety applications  | 
|---|---|---|
CompactLogix 5370, ControlLogix 5570, Compact GuardLogix 5370, and GuardLogix 5570 controllers  | Yes  | No  | 
CompactLogix 5380, CompactLogix 5480, ControlLogix 5580, Compact GuardLogix 5380, and GuardLogix 5580 controllers  | Yes  | Yes  | 
The BCD_TO instruction converts a BCD value (Source) to a decimal value and stores the result in the Destination.
     TIP: 
    In Logix Designer version 36, the mnemonic for this instruction changed from FRD to BCD_TO.
Available Languages
Ladder Diagram

Function Block Diagram
Function Block Diagram supports this element:
FBD Block

Structured Text
This instruction is not available in structured text. 
     IMPORTANT: 
    Unexpected operation may occur if:
          
- Output tag operands are overwritten.
 - Members of a structure operand are overwritten.
 - Except when specified, structure operands are shared by multiple instructions.
 
There are data conversion rules for mixing numeric data types within an instruction. See Data conversions. 
Ladder Diagram
Operand  | Data Type CompactLogix  5370, ControlLogix  5570, Compact GuardLogix  5370, and GuardLogix  5570 controllers | Data Type CompactLogix 5380, CompactLogix 5480, ControlLogix 5580, Compact GuardLogix 5380, and GuardLogix 5580 controllers  | Format  | Description  | 
Source  | SINT INT DINT  | SINT INT DINT LINT USINT UINT UDINT ULINT  | Immediate tag  | value to convert to decimal  | 
Destination  | SINT INT DINT  | SINT INT DINT LINT USINT UINT UDINT ULINT  | tag  | tag to store the result  | 
Function Block Diagram
FBD Block
Operand  | Type  | Format  | Description  | 
FRD tag  | FBD_CONVERT  | Structure  | FRD structure  | 
FBD_CONVERT Structure
Input Parameter  | Data Type  | Description  | 
EnableIn  | BOOL  | Enable input. If cleared, the instruction does not execute and outputs are not updated. Default is set.  | 
Source  | DINT  | Input to the conversion instruction.
                   Valid = any integer  | 
Output Parameters  | Data Type  | Description  | 
EnableOut  | BOOL  | Enable output.  | 
Dest  | DINT  | Result of the conversion instruction.  | 
Description
The BCD_TO instruction converts a BCD value (Source) to a decimal value and stores the result in the Destination.
This formula is used for calculations when source is 32bits:
Destination =(16#Source8*10
7
)+ (16#Source7*106
)+ (16#Source6*105
)+( 16#Source5*104
)+ (16#Source4*103
)+(16#Source3*102
)+ (16#Source2*101
)+( 16#Source1*100
)For example:
Source = 16#1234_567E
Destination = (1*10
7
)+(2*106
)+(3*105
)+ (4*104
)+(5*103
)+(6*102
)+(7*101
)+ (14*100
)=12345684Affects Math Status Flags
Major/Minor Faults
Controllers  | Affects Math Status Flags  | 
CompactLogix 5380, CompactLogix 5480, ControlLogix 5580, Compact GuardLogix 5380, and GuardLogix 5580 controllers  | Conditional, see .  | 
CompactLogix  5370, ControlLogix  5570, Compact GuardLogix  5370, and GuardLogix  5570 controllers | Yes  | 
None specific to this instruction. See Common Attributes for operand related faults.
Execution
Ladder Diagram
Condition/State  | Action Taken  | 
Prescan   | N/A  | 
Rung-condition-in is false  | Set Rung-condition-out to Rung-condition-in.  | 
Rung-condition-in is true  | Set Rung-condition-out to Rung-condition-in. Dest = decimal value of source with BCD value.  | 
Postscan  | N/A  | 
Function Block Diagram
FBD Block
Condition/State  | Action Taken  | 
Prescan  | N/A  | 
EnableIn is false  | Set EnableOut to EnableIn.  | 
EnableIn is true  | Dest = decimal value of source with BCD value If overflow occurs Clear EnableOut to false. else  Set EnableOut to true.  | 
Instruction first scan  | N/A  | 
Instruction first run  | N/A  | 
Postscan  | N/A  | 
Examples
Ladder Diagram

Function Block