Eliminates duplicate configurations
In a
FactoryTalk Batch
system using the OPC communication protocol and the Logix Designer
programming software, manually enter communication tag data for each of the ten standard tags and for each parameter, report, and additional request tag on each phase in FactoryTalk Batch Equipment Editor
. In Logix Designer
, manually create the corresponding tags. Each Tag Name
entered in Logix Designer
must match the Tag Item Name
entered in FactoryTalk Batch Equipment Editor
. Additionally, in Logix Designer
manually create the tags required for the PLI and FactoryTalk Batch
Server communications.In a
FactoryTalk Batch
system using Logix Designer
with PhaseManager
, the FactoryTalk Batch
Server communicates directly to the equipment phase objects in the Logix5000
controller; therefore, it is not necessary to enter any communication tag data in either application. In FactoryTalk Batch Equipment Editor
, tag names that match the parameters and reports defined on the phase are automatically created for each phase.PhaseManager
creates phases in FactoryTalk Batch Equipment Editor
or equipment phases in Logix Designer
, and synchronizes the FactoryTalk Batch
area model with the Logix Designer
project file. When synchronizing the area model with the project file, data types and tags are automatically created for each equipment phase and for all parameters and reports in Logix Designer
. It is not necessary to enter this information twice, in FactoryTalk Batch
and in Logix Designer
, as is required if OPC data servers are used with FactoryTalk Batch
.Any new equipment phases added in
Logix Designer
, or modifications to existing equipment phases in Logix Designer
, can also be transferred to the FactoryTalk Batch
area model when the FactoryTalk Batch
phases are synchronized with the Logix Designer
project.
NOTE:
Unsigned data types introduced in
Logix5000
version 32.00 are not supported by FactoryTalk Batch
. Configuring a FactoryTalk Batch
tag to reference a controller tag of any unsigned data type (USINT, UINT, UDINT, ULINT) will result in bad communication. If you attempt to run batches referencing any tags that include one of these data types a communication failure occurs at the point when the tag is used. Use
FactoryTalk Batch
Tag Verify
to produce a report that identifies any issues with the tag(s).Provide Feedback