Channel 1 - DF1 Master view parameters

The
Channel 1 - DF1 Master
view defines the characteristics of the DF1 Master.
The
Channel 1 - DF1 Master
view includes these parameters:
Parameter
Description
Station Address
Enter the station number of the channel. The valid range is from 0 through 254. The default is 0.
Transmit Retries
Enter the maximum number of times the Master retries sending message to Slave. Valid values are from 0 through 127. The default is 3.
ACK Timeout
Enter the maximum time, in 20 ms, the device waits for ACK for each message. Valid values are from 0 through 32767. The default is 50.
Reply Message Wait
Enter the minimum time, in 20 ms, between receiving an ACK and sending poll to slave. Valid values are from 0 through 65535. The default is 5.
Error Detection
Select Error Detection method:
  • BCC
  • CRC
Enable Duplicate Detection
Select to enable duplicate message detection.
Diagnostics
When online, opens the diagnostics dialog box to view diagnostic counters for performance and error management with the DF1 Master.
Provide Feedback