Chxx view parameters (5034-OF4IH)

The
Chxx
view includes these parameters:
Parameter
Description
Disable Channel
Determines whether the channel is disabled. Disable channels to prevent erroneous fault reporting, such as No Load or Open Wire faults, and to prevent the fault indication from the channel status indicator.
Output Type
Sets the output type for the channel. Available options are:
  • Voltage
  • Current
Output Range
Sets the output range for the output type. Ranges vary based on the selected Output Type.
Enable HART
Enables communication to HART devices.
Channel Offset
To compensate for any error in actuator operation, the module allows an offset to be added to the output channel value sent from the controller. Values are entered in Engineering Units (EU). The default value for the channel offset is 0.0.
Hold for Initialization
When set, configures the channel to hold, or not change, until initialized with a value within 0.1% of full scale of its current value when one of the following conditions occurs.
  • Module initial connection (powerup)
  • Controller transition from Program Mode back to Run Mode
  • Module re-establishes communication after a fault
  • SA power is restored after being lost.
Enable No Load Detection
Enables the detection of whether a load has been disconnected.
  • If selected, the module detects when a wire is disconnected from the channel or a missing load for the output channel.
  • If cleared, the module does not detect when a wire is disconnected from the channel or a missing load for the output channel.
IMPORTANT:
This option is available only if the Input Type is Current.
High Signal
Sets one of the four constants in the scaling equation. High Signal is in terms of the input signal units and corresponds to High Engineering when scaled.
Low Signal
Sets one of the four constants in the scaling equation. Low Signal is in terms of the input signal units and corresponds to Low Engineering when scaled.
Engineering Units
Sets the unit of measurement for High Engineering and Low Engineering.
High Engineering
Sets one of the four constants in the scaling equation. High Engineering corresponds to High Signal and helps determine the engineering units that the signal values scale into.
Low Engineering
Sets one of the four constants in the scaling equation. Low Engineering corresponds to Low Signal and helps determine the engineering units that the signal values scale into.
Recalculate Units
Recalculates new values to the following configuration parameters in Engineering Units based on the new Scaling constants.
  • Low Clamp
  • High Clamp
  • User Defined Value in Program Mode
  • User Defined Value in Fault Mode
  • Final Communication Fault State Value
  • Ramp Rate
  • Channel Offset
TIP: This option is enabled when any of the four Scaling constants is changed.
Output State in Program Mode
Determines channel action when the controller transitions to Program Mode or Inhibit mode.
  • Hold Last State causes the output to remain at the last value that is sent from the controller before being placed in Program Mode or Inhibit mode.
  • User Defined Value forces the output to whatever value is entered in the field. The value is entered on Chxx in the engineering units defined by the scaling parameters for the channel.
When Communication Fails in Program Mode
  • Leave outputs in Program Mode state causes the output to behave as defined by the Output State in Program Mode selection.
  • Change outputs to Communication Fault Mode state causes the output to behave as defined by the Output State in Communication Fault Mode selection.
    After the defined duration has elapsed, the output goes to the Final Communication Fault State Value, entered in engineering units.
Output State in Communication Fault Mode
Determines channel action when a communication fault occurs.
  • Hold Last State causes the output to remain at the last value that is sent from the controller before loss of communication.
  • User Defined Value forces the output to whatever value is entered in the field. The value is entered in the engineering units defined by the scaling parameters for the channel.
Communication Fault State Duration
Determines the length of time the FaultValue value is held before the FinalFaultState.
Final Communication Fault State Value
Defines the value, in Engineering Units, to which the output goes after the Communication Fault State Duration time expires.
Diagnostics
Accesses the Diagnostics dialog, which contains diagnostics information for the channel.