Alarms view parameters

The
Alarms
view include these parameters:
Parameter
Description
Disable All Alarms
Prevents the module from generating any of the four process alarms (Low Low, Low, High, and High High) or the Rate Alarm and does not allow access to any of the alarm configuration properties.
IMPORTANT: To use alarms, set the Chxx.AlarmDisable configuration tag to 1. Also, make sure that the Chxx.yyAlarmEn output tag for the same channel is set to 1.
Latch Process Alarms
Instructs the module to latch any of the four process alarms (Low Low, Low, High, and High High) once the alarm has been triggered, even if the condition causing the alarm to occur disappears.
High High Limit
Sets the trigger point in Engineering Units. HHAlarm tag is set to 1 when the input signal moves above this limit.
High Limit
Sets the trigger point in Engineering Units. HAlarm tag is set to 1 when the input signal moves above this limit.
Low Limit
Sets the trigger point in Engineering Units. LAlarm tag is set to 1 when the input signal moves below this limit.
Low Low Limit
Sets the trigger point in Engineering Units. LLAlarm tag is set to 1 when the input signal moves below this limit.
Deadband
Allows the process alarm status bits to remain set, even if the alarm condition disappears, as long as the channel data remains within plus or minus the deadband value of the process alarm. This Deadband value is entered in engineering units.
Enable Rate Alarm Latching
Latches the Rate Alarm so that it does not clear until explicitly unlatched.
Rate Alarm Limit
Sets the trigger point in Engineering Units per second. RateAlarm tag is set to 1 when the rate of change between input samples on this channel exceeds this limit.