Analyzer Remote Control
Mode change - Status
(class 0x313, instance 1, attribute 24)
State of mode change request interface (0=ready).
Mode change - Request
(class 0x313, instance 1, attribute 21)
Mode change request
Value | Request |
|---|---|
0 | None |
1 | Enter fieldbus mode |
2 | Continue automatic mode |
3 | Restart automatic mode |
Action request - Status
(class 0x313, instance 1, attribute 25)
Manual action request state. 0 = ready.
Action request - Manual Request
(class 0x313, instance 1, attribute 23)
Manual activity request.
Value | Request |
|---|---|
0 | None |
1 | Start measurement |
2 | Start calibration |
3 | Start cleaning |
Action request - Abort Request
(class 0x313, instance 1, attribute 22)
Abort current activity.
Value | Request |
|---|---|
0 | None |
1 | Abort current action |
Provide Feedback