Module Data Types 1794-OB8EP
The table below lists and describes the module-defined data types for the 1794-OB8EP Digital Output module. It includes information for input (as indicated by an "I"), output (as indicated by an "O"), and configuration (as indicated by a "C").
TIP:
FLEX I/O is based on 16-bit INTs and not 32-bit
DINTs. Using 16-bit INTs in instructions that are optimized for 32-bit DINTs may decrease
performance with certain instructions.
Module-defined Data Type: AB:1794_DO_EFused:I:0
This module-defined data type does not apply to modules having Rack Optimization selected for the Comm Format and does not appear among the Module Tags in the RSLogix software.
Member Name | Type | Default Display Style | Description |
Fault | DINT | Binary | Fault - Used for Input Data Validation 0 = Valid Data 1 = Invalid Data - if the connection to the module has been lost, or if the module has a severe hardware fault, the lower 8 bits are set to 1. |
Status | INT | Binary | |
OverLoadFault_8 | BOOL | Decimal | Fault Overload Status. |
OverLoadFault_9 | BOOL | Decimal | Fault Overload Status. |
OverLoadFault_10 | BOOL | Decimal | Fault Overload Status. |
OverLoadFault_11 | BOOL | Decimal | Fault Overload Status. |
OverLoadFault_12 | BOOL | Decimal | Fault Overload Status. |
OverLoadFault_13 | BOOL | Decimal | Fault Overload Status. |
OverLoadFault_14 | BOOL | Decimal | Fault Overload Status. |
OverLoadFault_15 | BOOL | Decimal | Fault Overload Status. |
Module-defined Data Type: AB:1794_DO_Efused:O:0
Member Name | Type | Default Display Style | Description |
Data | SINT | Binary | Safe state data using Points 0 through 15. |
Control | SINT | Binary | |
FaultReset | BOOL | Decimal | Output reset bit. |
Module-defined Data Type: AB:1794_DO8:C:0
Member Name | Type | Default Display Style | Description |
SSData | SINT | Binary | Safe state data. |
Provide Feedback