UA Tag List

How do I open UA Tag List?
  1. From the
    Start
    menu, select
    Rockwell Software > FactoryTalk Linx Gateway Configuration
    .
  2. On
    OPC UA Server
    , under
    Namespace
    , select
    Tag list and structures/array access
    .
  3. On the left pane, select
    UA Tag List
    .
The UA tag list configuration determines the data values that each OPC UA Client can access from
FactoryTalk Linx Gateway
. The UA tag list option provides both enhanced security and complex type information (for example, structures and arrays). When the Folders with scalar data option is enabled, all tags that are available from data sources in a FactoryTalk Application (for example, controllers and hardware via
FactoryTalk Live
, OPC DA and OPC UA servers) are accessible as scalar values to OPC UA Clients. The UA tag list contains one or more tag groups that define access rights and includes complex type information enabling an OPC UA Client to utilize structures or User Defined Types (UDT) from Logix controllers.
Use
UA
Tag List
to view and edit the tag group, add tags to the tag group and set tag access rights.
FactoryTalk Linx Gateway
provides the ability to create tag groups, which includes a subset of data tags in the
FactoryTalk
system and to add one tag to multiple tag groups. By configuring the tag group access rights with users,
FactoryTalk Linx Gateway
limits the
OPC
UA Client's access to this group of tags instead of exposing all the tags and manages accesses to different groups of clients. Users who are not given access to a tag group in FactoryTalk Security will have no access to the tags in the tag group.
UA Tag List
is also required if the OPC UA Client must access structured type information.
Only the tags configured in the tag group can be added to namespace can be access by the OPC UA client.
Use
UA Tag List
to add the following tags:
  • Structure and array and its elements separately.
    TIP:
    If an element is added while the structure itself is not added, the structure will be added as a folder, and the rest elements under the structure will not be added automatically.
    If you add a structure or array in the
    UA Tag List
    , the exact structure or array will show in
    OPC
    UA Client.
  • Scalar.
  • Folder (for example, Shortcut to a Logix controller or program in a Logix controller and all its contents). OPC UA Client is able to find the tags under the folder in a real-time and dynamic way. When the tags in the
    Tag Browsed
    pane are changed, re-browse to find the updated tags.
TIP:
The UA tag list does not support FactoryTalk Diagnostic Audit message.
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.