Configure point properties (5094-OB16S, -OW4IS)
Configure the point properties for the 5094-OB16S and 5094-OW4IS modules.
To configure point properties (5094-OB16S and -OW4IS):
- In theController Organizer, expand theI/O Configurationfolder, and double-click the module.
- SelectPoints.
- For the 5094-OB16S module, inPoint Operation Type, select single or dual channel output.
- InPoint Mode, select the operation mode for the point.
- For each point, select or clearEnable No Load Diagnosticif applicable.Tip:IfPoint Operation TypeisDual, the two output points must use the sameEnable No Load Diagnosticcheck box setting.
- InOutput State During Program Mode and Communications Fault Mode, select thebehavior of each output when the controller transitions to Program mode.
- (optional) If available, selectDiagnosticsto view the point's diagnostic information.
- InLatch Fault until reset via output tag, select enable or disable a latch fault until reset via output tag.
- SelectOK.