Power Wiring and Grounding—Frames 5, 6, and 6L
The safety ground-PE must be connected to system ground. Ground impedance must conform to the requirements of national and local industrial safety regulations and/or electrical codes. The integrity of all ground connections should be periodically checked.
This diagram shows products connected to a solid ground single point (PE only) power source. Some applications may require alternate grounding schemes, see Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives, publication DRIVES-IN001, for more information. These applications include installations with long distances between drives or drive line-ups, which could cause large potential differences between the drive or line-up grounds.
For installations within a cabinet, a single safety ground point or ground bus bar connected directly to building steel should be used. All circuits including the AC input ground conductor should be grounded independently and directly to this point/bar.
Typical Grounding—Frames 5, 6, and 6L
Provide Feedback