Example: Read Elapsed Life for a 100-E Motor Starter (Motor Starts)
You can view the following predictive maintenance data for a 100-E motor via Module Properties:
- Remaining life
- Elapsed life
- Consumed life percentages
You can use a message instruction to access elapsed life data.
Message Instruction to Read Elapsed Life

Message Configuration to Read Elapsed Life

Parameter | Value | Description |
|---|---|---|
Service Type | Get Attribute Single | Type of message |
Service Code | 0E | Motor starter object |
Class | 414 | Predictive maintenance component object |
Instance | 1 | — |
Attribute | 4 | Elapsed life |
Data type | UDINT | Number of operations |
Select the path to the 100-E motor device on the Communication tab.