Trend considerations
Understand the requirements and limitations for trend configuration and
capturing.
Trend configuration
- A trend must contain at least one tag before trend capturing can start.
- All tags in a trend must belong to the same controller. The first tag added to the trend determines the controller used for the trend.
- You can add up to 32 tags to a trend.
- Use thePropertiespane to edit the trend name and description.
- You cannot modify tags or the sample period during trend capturing.
- TheMin,Max, andAveragevalues in the trend tab display statistics collected during trend capturing. These values are different from theMinandMaxsettings in the trend configuration tab, which define the configured value range for the tag.
Trend capturing
- You cannot start a trend if another active trend uses the same tag set and sample period. Modify the tag selection or sample period before starting the trend.
- A trend continues capturing when the trend tab is open but not in focus.
- A trend can capture data for up to 24 hours. After 24 hours, the newer data will replace the oldest captured data.
- All tags in a trend start and stop capturing together.
- A maximum of eight trends can capture data simultaneously per controller.
- Closing a capturing trend stops data capture and discards the collected data.
- Stopping a trend discards the captured data and resets the chart.
- Trend capturing stops if the controller becomes unavailable.
- Trend capturing stops when the browser is closed or when you manually sign out ofFactoryTalk Design Studio.
- Automatic sign-out fromFactoryTalk Design Studiois disabled while a trend is capturing.
Provide Feedback