1834-AENTR Gateway Status Indicators

See the status indicators on your device to identify its current status.
1834-AENTR Gateway Status Indicators
Status indicators
1834-AENTR Gateway Status Indicators
Status Indicator
State
Description
NET
Network status for the
EtherNet/IP
network
Off
The gateway is powered off or powered on, but no IP address configured.
Flashing Green
An IP address is configured, but no
CIP
connections are established.
Steady Green
The gateway has an IP address, established at least 1
CIP
connection, and is operating properly.
Flashing Red
The gateway has an IP address but a
CIP
connection has timed out.
Red
The gateway shares an IP address with another device on the network. Change the IP address of the module.
Flashing Green and Red
The gateway is performing its power-up testing.
LINK1
LINK2
Status of data transmission
Off
Either the module is not powered on or a cable does not exist on the port.
Flashing Green
Activity exists on the port at 1000 MB or 100 MB.
Steady Green
A 1000 MB or 100 MB link exists on the port, but no traffic is being received.
Flashing Yellow
Activity exists on the port at 10 MB.
Steady Yellow
10 MB link exists on the port, but no traffic is being received.
MNS
Module and
EtherNet/IP
In-cabinet network status
Off
IP addresses are not configured on the bus.
Flashing Green
IP addresses are configured on the bus but there are no connections.
Steady Green
IP addresses are configured, at least 1 connection is established, and the bus is operating properly.
Flashing Red
IP addresses are configured but connections have timed out or a major recovery fault has occurred.
Steady Red
A device on the bus has the same IP address or the internal diagnostics has created a non-resettable fault.
IMPORTANT: If a duplicate IP address fault is not present and the fault persists through power cycles, the device should be replaced.
Flashing Green and Red
The device is performing its power-up testing.
N PWR
Network power status
Off
The power supply is off.
Steady Green
The power supply is operating correctly.
Steady Red
The power supply in a tripped state.
Flashing Red
The power supply is in a warning state.
S PWR
Switched power status
Off
The power supply is off.
Steady Green
The power supply is operating correctly.
Steady Red
The power supply in a tripped state.
Flashing Red
The power supply is in a warning state.
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.
Normal