Example: Read Elapsed Life for a 100-E Motor Starter (Motor Starts)

You can view the following predictive maintenance data for a 100-E motor via Module Properties:
  • Remaining life
  • Elapsed life
  • Consumed life percentages
You can use a message instruction to access elapsed life data.
Message Instruction to Read Elapsed Life
Message instruction to read elapsed life
Message Configuration to Read Elapsed Life
Message configuration to read elapsed life
Class, Instance, and Attribute Values for Elapsed Life
Parameter
Value
Description
Service Type
Get Attribute Single
Type of message
Service Code
0E
Motor starter object
Class
414
Predictive maintenance component object
Instance
1
Attribute
4
Elapsed life
Data type
UDINT
Number of operations
Select the path to the 100-E motor device on the Communication tab.