1834-SUP-PWR Status Indicators

See the status indicators on your device to identify its status.
1834-SUP-PWR Supplemental Power Tap Status Indicators
Status indicators
1834-SUP-PWR Status Indicators
Status Indicator
State
Description
MNS
Module and
EtherNet/IP
In-cabinet network status
Off
IP addresses are not configured on the bus.
Flashing Green
IP addresses are configured on the bus but there are no connections.
Steady Green
IP addresses are configured, at least 1 connection is established, and the bus is operating properly.
Flashing Red
IP addresses are configured but connections have timed out or a major recovery fault has occurred.
Steady Red
A device on the bus has the same IP address or the internal diagnostics has created a non-resettable fault.
IMPORTANT:
If a duplicate IP address fault is not present and the fault persists through power cycles, the device should be replaced.
Flashing Green and Red
The device is performing its power-up testing.
S PWR
Power status for the supplemental power tap
Steady green
Switched channel is operating properly.
Steady red
Switched channel is in a tripped state.
Flashing Red
Switched channel is in a warning state.
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.