Points view parameters

The
Points
view includes these parameters:
Parameter
Description
Point
Displays the point number to configure.
Input Filter Time
Off
®
On
Sets the value which maps to an off to on filter time.
Use the off to on time to set a delay in responding to transitions from off to on. The off to on time is useful for filtering out transients in noisy environments. Available values are:
  • 0 = 0
    m
    s (default)
  • 13 = 1 ms
  • 14 = 2 ms
  • 15 = 5 ms
  • 16 = 10 ms
  • 17 = 20 ms
  • 18 = 50 ms
Input Filter Time
On
®
Off
Sets the value which maps to an on to off filter time.
Use the on to off time to set a delay in responding to transitions from on to off. The on to off time is useful for filtering out transients in noisy environments. Available values are:
  • 0 = 0
    m
    s (default)
  • 13 = 1 ms
  • 14 = 2 ms
  • 15 = 5 ms
  • 16 = 10 ms
  • 17 = 20 ms
  • 18 = 50 ms
Type 3-d Open Wire Detection
Enables open wire detection on the point when selected.
Type 3-d Open Wire Detection
is not available in Run mode.
Tip
:
Type 3-d Open Wire Detection
is visible when Discrete device type is IEC 61131-2 Type 3-d Digital Input.
Type 3-d Short Circuit Detection
Enables short circuit detection on the point when selected.
Type 3-d Short Circuit Detection
is not available in Run mode.
Tip
:
Type 3-d Short Circuit Detection
is visible when Discrete device type is IEC 61131-2 Type 3-d Digital Input.
Diagnostics
Opens
Points Diagnostics
.