Device-defined data type: AB:5000_AO8:I:0
Connection Type: Data and Listen Only
Member Name
Type
Style
Valid Values
RunMode
BOOL
Decimal
0 = Idle
1 = Run
  • Output products follow the Run mode of the owning connection.
  • Input-only products are always in Run mode.
ConnectionFaulted
BOOL
Decimal
0 = A connection exists between the device and the controller.
1 = Not connected
DiagnosticActive
BOOL
Decimal
0 = No diagnostics active
1 = One or more diagnostics are active or the prognostics threshold is reached
DiagnosticSequenceCount
SINT
Decimal
-128 to 127
Increments each time a distinct diagnostic condition is detected, and each time a distinct diagnostic condition transitions from detected to not detected. The value of 0 is skipped except during device power-up.
Ch0x.Fault
BOOL
Decimal
0 = No fault exists
1 = Fault exists
A fault is a roll-up of all of the diagnostic conditions that the device can detect and indicates bad data. If there is a detailed data type member that indicates a given detected condition, this fault member does not affect the DiagnosticActive or DiagnosticSequenceCount members. However, if there is no detailed data type for a given detected condition, this fault member triggers both the DiagnosticActive member and increments/decrements the Diagnostic Sequence Count.
Ch0x.Uncertain
BOOL
Decimal
0 = Valid data
1 = Data validity uncertain. Device is operating outside its designed operating range, or data is under manual or override control.
Ch0x.NoLoad
BOOL
Decimal
0 = No load condition does not exist
1 = No load condition exists, meaning a signal wire is disconnected from the channel or the RTB.
Ch0x.ShortCircuit
BOOL
Decimal
0 = No short circuit or overcurrent condition exists
1 = Short circuit or overcurrent exists
Ch0x.OverTemperature
BOOL
Decimal
0 = Device temperature is not over the operating limits
1 = Device temperature is over the operating limits
Ch0x.FieldPowerOff
BOOL
Decimal
0 = Field power is present
1 = Field power is not present
Ch0x.InHold
BOOL
Decimal
0 = Channel is not holding
1 = Channel is holding
Ch0x.NotANumber
BOOL
Decimal
0 = Last channel data received was a number
1 = Output value received from the originator is NotANumber (the IEEE NAN value). The output channel holds its last state
Ch0x.Underrange
BOOL
Decimal
0 = The input signal at the channel is greater than the minimum detectable signal.
1 = The input signal at the channel is less than or equal to the minimum detectable signal.
Ch0x.Overrange
BOOL
Decimal
0 = The input signal at the channel is less than the maximum detectable signal.
1 = The input signal at the channel is greater than or equal to the maximum detectable signal.
Ch0x.LLimitAlarm
BOOL
Decimal
0 = Alarm is not triggered
1 = Alarm is triggered
Ch0x.HLimitAlarm
BOOL
Decimal
0 = Alarm is not triggered
1 = Alarm is triggered
Ch0x.RampAlarm
BOOL
Decimal
0 = Alarm is not triggered
1 = Alarm is triggered
Ch0x.CalFault
BOOL
Decimal
0 = Calibration did not fail
1 = A calibration session for a channel was interrupted or failed. CalFault is reset by product reset or power cycle.
Ch0x.Calibrating
BOOL
Decimal
0 = Channel is not being calibrated
1 = Channel is being calibrated
Ch0x.Data
REAL
Float
-1.0E11 to 1.0E11
Ch0x.RollingTimestamp
INT
Decimal
Any positive value.
RollingTimestamp is a continuously running timer that counts in milliseconds. When an input device scans its channels, it also records the RollingTimestamp value.
Device-defined data type: AB:5000_AO8:O:0
Connection Type: Data
Member Name
Type
Style
Valid Values
Ch0x.LLimitAlarmUnlatch
BOOL
Decimal
Transition from low to high unlatches alarm.
Ch0x.HLimitAlarmUnlatch
BOOL
Decimal
Transition from high to low unlatches alarm.
Ch0x.RampAlarmUnlatch
BOOL
Decimal
Transition from low to high unlatches alarm
Ch0x.Data
REAL
Float
-1.0E11 to 1.0E11
Device-defined data type: AB:5000_AO8_HART:C:0
Connection Type: Data
Member Name
Type
Style
Valid Values
Ch0x.AlarmDisable
BOOL
Decimal
0 = Alarms are enabled
1 = Alarms are disabled (default)
Ch0x.LimitAlarmLatchEn
BOOL
Decimal
0 = Latching disabled (default)
1 = Latching enabled
Ch0x.RampAlarmLatchEn
BOOL
Decimal
0 = Latching disabled (default)
1 = Latching enabled
Ch0x.NoLoadEn
BOOL
Decimal
0 = Disabled (default)
1 = Enabled
Ch0x.Disable
BOOL
Decimal
0 = Channel is enabled (default)
1 = Channel is disabled
Ch0x.FaultMode
BOOL
Decimal
0 = Transition to user-defined value
1 = Hold Last State (default)
Ch0x.ProgMode
BOOL
Decimal
0 = Transition to user-defined value
1 = Hold Last State (default)
Ch0x.ProgramToFaultEn
BOOL
Decimal
0 = Channel remains in Program mode
1 = Channel transitions to Fault mode
Ch0x.RampInRun
BOOL
Decimal
0 = Ramping disabled (default)
1 = Ramping enabled in Run mode
Ch0x.RampToProg
BOOL
Decimal
0 = Ramping disabled (default)
1 = Ramping enabled to Program mode state
Ch0x.RampToFault
BOOL
Decimal
0 = Ramping disabled (default)
1 = Ramping enabled to Fault mode state
Ch0x.HoldForInit
BOOL
Decimal
0 = Unchecked
1 = Checked
Ch0x.FaultValueStateDuration
SINT
Decimal
0 = Forever
1 = 1 second
2 = 2 seconds
5 = 5 seconds
10 seconds
Ch0x.MaxRampRate
REAL
Float
0 to 1.0E11
Ch0x.LowSignal
REAL
Float
-1.0E11 to 1.0E11
A combination of LowSignal, HighSignal, LowEngineering, and HighEngineering are used to scale the input data returned by the device.
Ch0x.HighSignal
REAL
Float
-1.0E11 to 1.0E11
A combination of LowSignal, HighSignal, LowEngineering, and HighEngineering are used to scale the input data returned by the device.
Ch0x.LowEngineering
REAL
Float
-1.0E11 to 1.0E11
A combination of LowSignal, HighSignal, LowEngineering, and HighEngineering are used to scale the input data returned by the device.
Ch0x.HighEngineering
REAL
Float
-1.0E11 to 1.0E11
A combination of LowSignal, HighSignal, LowEngineering, and HighEngineering are used to scale the input data returned by the device.
Ch0x.LowLimit
REAL
Float
-1.0E11 to 1.0E11
Ch0x.HighLimit
REAL
Float
-1.0E11 to 1.0E11
Ch0x.Offset
REAL
Float
-1.0E11 to 1.0E11
Ch0x.FaultValue
REAL
Float
-1.0E11 to 1.0E11
Ch0x.ProgValue
REAL
Float
-1.0E11 to 1.0E11
Ch0x.FaultFinalState
REAL
Float
-1.0E11 to 1.0E11