Device-defined data types (5094-IF8IH, 5094-IF8IHXT)

Device-defined data type names vary for each device depending on selections made when creating the device.
These tables list and describe device-defined data types for the 5094-IF8IH or 5094-IF8IHXT devices.
These tables include this information:
  • input (as indicated by an "I")
  • output (as indicated by an "O")
  • configuration (as indicated by a "C")
Device-defined data type: AB:5000_AI8:I:0, AB:5000_AI4_DI4:I:0, AB:5000_AI4_DI4_Type3d:I:0, AB:5000_DI8:I:0, AB:5000_DI8_Type3d:I:0
Connection Type: Data and Listen Only
Member Name
Type
Style
Valid Values
RunMode
BOOL
Decimal
0 = Idle
1 = Run
  • Output products follow the Run mode of the owning connection.
  • Input-only products are always in Run mode.
ConnectionFaulted
BOOL
Decimal
0 = A connection exists between the device and the controller.
1 = Bad
DiagnosticActive
BOOL
Decimal
0 = No diagnostics active
1 = One or more diagnostics are active or the prognostics threshold is reached.
DiagnosticSequenceCount
SINT
Decimal
-128 to 127
Increments each time a distinct diagnostic condition is detected, and each time a distinct diagnostic condition transitions from detected to not detected. The value of 0 is skipped except during device power-up.
Ch0x.Fault
BOOL
Decimal
0 = No fault exists
1 = Fault exists
A fault is a roll-up of all the diagnostic conditions that the device can detect and indicates bad data. If there is a detailed data type member that indicates a given detected condition, this fault member does not affect the DiagnosticActive or DiagnosticSequenceCount members. However, if there is no detailed data type for a given detected condition, this fault member triggers both the DiagnosticActive member and increments/decrements the Diagnostic Sequence Count.
Ch0x.Uncertain
BOOL
Decimal
0 = Valid data
1 = Data validity uncertain. Device is operating outside its designed operating range, or data is under manual or override control.
Ch0x.OpenWire
BOOL
Decimal
0 = Open wire condition does not exist or open wire detection is disabled.
1 = Open wire condition exists, meaning the signal wire is disconnected from the channel or the RTB.
Ch0x.OverTemperature
BOOL
Decimal
0 = Device temperature is not over the operating limits
1 = Device temperature is over the operating limits
Ch0x.FieldPowerOff
BOOL
Decimal
0 = Field power is present
1 = Field power is not present
Ch0x.NotANumber
BOOL
Decimal
0 = Last channel data received was a number
1 = Last channel data received was not a number
Ch0x.Underrange
BOOL
Decimal
0 = The input signal at the channel is greater than the minimum detectable signal.
1 = The input signal at the channel is less than or equal to the minimum detectable signal.
Ch0x.Overrange
BOOL
Decimal
0 = The input signal at the channel is less than the maximum detectable signal.
1 = The input signal at the channel is greater than or equal to the maximum detectable signal.
Ch0x.LLAlarm
BOOL
Decimal
0 = Alarm is not triggered
1 = The input signal has moved below the configured Low Low Alarm Limit. It remains set until the signal moves above the configured Low Low Alarm Limit plus Deadband if specified.
Ch0x.LAlarm
BOOL
Decimal
0 = Alarm is not triggered
1 = The input signal moved below the configured Low Alarm Limit. It remains set until the signal moves above the configured Low Alarm Limit plus Deadband if specified.
Ch0x.HAlarm
BOOL
Decimal
0 = Alarm is not triggered
1 = The input signal moved above the configured High Alarm Limit. It remains set until the signal moves below the configured High High Alarm Limit minus Deadband if specified.
Ch0x.HHAlarm
BOOL
Decimal
0 = Alarm is not triggered
1 = The input signal moved above the configured High High Alarm Limit. It remains set until the signal moves below the configured High High Alarm Limit minus Deadband if specified.
Ch0x.RateAlarm
BOOL
Decimal
0 = Alarm is not triggered
1 = The input channel’s rate of change exceeds the configured rate alarm. It remains set until the rate of change drops below the configured rate.
Ch0x.CalFault
BOOL
Decimal
0 = Calibration did not fail
1 = A calibration session for a channel was interrupted or failed. CalFault is reset by product reset or power cycle.
Ch0x.Calibrating
BOOL
Decimal
0 = Channel is not being calibrated
1 = Channel is being calibrated
Ch0x.Data
REAL
Float
-1.0E11 to 1.0E11
Ch0x.RollingTimestamp
INT
Decimal
Any positive value.
RollingTimestamp is a continuously running timer that counts in milliseconds. When an input device scans its channels, it also records the RollingTimestamp value.
Pt0x.Fault
Pt0x.Pt.Fault
BOOL
Decimal
0 = No fault exists
1 = Fault exists
A fault is a roll-up of all the diagnostic conditions that the device can detect and indicates bad data. If there is a detailed data type member that indicates a given detected condition, this fault member does not affect the DiagnosticActive or DiagnosticSequenceCount members. However, if there is no detailed data type for a given detected condition, this fault member triggers both the DiagnosticActive member and increments/decrements the Diagnostic Sequence Count.
Pt0x.Data
Pt0x.Pt.Data
BOOL
Decimal
0 = Input is Off
1 = Input is On
Pt0x.Uncertain
Pt0x.Pt.Uncertain
BOOL
Decimal
0 = Valid data
1 = Data validity uncertain
Device is operating outside its designed operating range.
Pt0x.Type3dOpenwire
BOOL
Decimal
0 = Type 3-d Open Wire is not detected
1 = Type 3-d Open Wire is detected
Pt0x.Type3dShortcircuit
BOOL
Decimal
0 = Type 3-d Short Circuit is not detected
1 = Type 3-d Short Circuit is detected
Device-defined data type: AB:5000_AI8:O:0, AB:5000_AI4:O:0
Connection Type: Data
Member Name
Type
Style
Valid Values
Ch0x.LLAlarmEn
BOOL
Decimal
0 = Alarm is disabled
1 = Alarm is enabled
Ch0x.LAlarmEn
BOOL
Decimal
0 = Alarm is disabled
1 = Alarm is enabled
Ch0x.HAlarmEn
BOOL
Decimal
0 = Alarm is disabled
1 = Alarm is enabled
Ch0x.HHAlarmEn
BOOL
Decimal
0 = Alarm is disabled
1 = Alarm is enabled
Ch0x.RateAlarmEn
BOOL
Decimal
0 = Alarm is disabled
1 = Alarm is enabled
Ch0x.LLAlarmUnlatch
BOOL
Decimal
Transition from low to high unlatches alarm.
Ch0x.LAlarmUnlatch
BOOL
Decimal
Transition from low to high unlatches alarm.
Ch0x.HAlarmUnlatch
BOOL
Decimal
Transition from high to low unlatches alarm.
Ch0x.HHAlarmUnlatch
BOOL
Decimal
Transition from high to low unlatches alarm.
Ch0x.RateAlarmUnlatch
BOOL
Decimal
Transition from low to high unlatches alarm.
Ch0x.SensorOffset
REAL
Float
-1.0E11 to 1.0E11
A user-defined offset in engineering units added directly into the scaled data, used to compensate for inherent sensor offset. Commonly used with thermocouple sensors to offset accuracy issues.
Device-defined data type: AB:5000_AI8_HART:C:0, AB:5000_AI4_DI4:C:0, AB:5000_AI4_DI4_Type3d:C:0
Connection Type: Data
Member Name
Type
Style
Valid Values
Ch0x.SensorType
SINT
Decimal
Not applicable to this device
Ch0x.NotchFilter
SINT
Decimal
0 = 10 Hz
1 = 50 Hz
2 = 60 Hz (default)
3 = 100 Hz
4 = 200 Hz
5 = 500 Hz
6 = 1,000 Hz
7 = 2,500 Hz
8 = 5,000 Hz
9 = 10,000 Hz
13 = 5 Hz
15 = 15 Hz
16 = 20 Hz
Ch0x.AlarmDisable
BOOL
Decimal
0 = Alarms are enabled
1 = Alarms are disabled (default) for the channel
Ch0x.ProcessAlarmLatchEn
BOOL
Decimal
0 = Latching disabled (default)
1 = Latching enabled for all four process alarms: low low, low, high and high high. Latching causes the process alarm to remain set until an unlatch service is explicitly sent to the channel or alarm.
Ch0x.RateAlarmLatchEn
BOOL
Decimal
0 = Latching disabled (default)
1 = Latching enabled for the rate alarm. Latching causes the rate alarm to remain set until an unlatch service is explicitly sent to the channel or alarm.
Ch0x.OpenWireEn
BOOL
Decimal
0 = Disabled (default)
1 = Enabled detection when the signal wire is disconnected from one of its channels or the RTB.
Ch0x.Disable
BOOL
Decimal
0 = Channel is enabled (default)
1 = Channel is disabled
Ch0x.TenOhmOffset
INT
Decimal
-1.00 to 1.00 ohms
Offset used to linearize a 10 Ω copper sensor type’s input.
Ch0x.DigitalFilter
INT
Decimal
0 to 32,767 ms
Time constant, in milliseconds, used in a first order lag filter to smooth the input signal.
Ch0x.LowSignal
REAL
Float
-1.0E11 to 1.0E11
A combination of LowSignal, HighSignal, LowEngineering, and HighEngineering are used to scale the input data returned by the device.
Ch0x.HighSignal
REAL
Float
-1.0E11 to 1.0E11
A combination of LowSignal, HighSignal, LowEngineering, and HighEngineering are used to scale the input data returned by the device.
Ch0x.LowEngineering
REAL
Float
-1.0E11 to 1.0E11
A combination of LowSignal, HighSignal, LowEngineering, and HighEngineering are used to scale the input data returned by the device.
Ch0x.HighEngineering
REAL
Float
-1.0E11 to 1.0E11
A combination of LowSignal, HighSignal, LowEngineering, and HighEngineering are used to scale the input data returned by the device.
Ch0x.LLAlarmLimit
REAL
Float
-1.0E11 to 1.0E11
The low low alarm trigger point.
Ch0x.LAlarmLimit
REAL
Float
-1.0E11 to 1.0E11
The low alarm trigger point.
Ch0x.HAlarmLimit
REAL
Float
-1.0E11 to 1.0E11
The high alarm trigger point.
Ch0x.HHAlarmLimit
REAL
Float
-1.0E11 to 1.0E11
The high high alarm trigger point.
Ch0x.RateAlarmLimit
REAL
Float
0.0 to 1.0E11
Ch0x.AlarmDeadband
REAL
Float
0.0 to 1.0E11
Pt0x.InputOffOnFilter
SINT
Decimal
Off to On digital filter
  • 13 = 1 ms
  • 14 = 2 ms
  • 15 = 5 ms
  • 16 = 10 ms
  • 17 = 20 ms
  • 18 = 50 ms
Pt0x.InputOnOffFilter
SINT
Decimal
On to Off digital filter
  • 13 = 1 ms
  • 14 = 2 ms
  • 15 = 5 ms
  • 16 = 10 ms
  • 17 = 20 ms
  • 18 = 50 ms
Pt0x.Type3dOpenWireEn
BOOL
Decimal
0 = disable Type 3-d Open Wire detection
1 = enable Type 3-d Open Wire detection
Pt0x.Type3dShortCircuitEn
BOOL
Decimal
0 = disable Type 3-d Short Circuit detection
1 = enable Type 3-d Short Circuit detection